Siemens SIMATIC TI500 Manuel d'utilisateur Page 76

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 94
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 75
Modbus Commands
C-27
TIWAY I Gateway User Manual
This
command permits the collection of constant (K) memory
. The formats of
the command and response are as follows.
I000000
Request: aa 42 llll nnnn XXXX
Checksum (XXXX)
Number of locations to collect (nnnn)
Starting location to collect from (llll)
Command 66 (42 hex)
Address (aa)
Figur
e C-33
Command
66 — Request
I000000
Response: aa 42 bb dddd . . . XXXX
Checksum (XXXX)
K-memory data
Number of data bytes to follow (bb)
Command 66 (42 hex)
PLC TIWAY network address (aa)
Figur
e C-34
Command
66 — Response
This command permits the collection of W
ord Output memory
. The formats
of the command and response are as follows.
I000000
Request: aa 43 llll nnnn XXXX
Checksum (XXXX)
Number of locations to collect (nnnn)
Starting location to collect from (llll)
Command 67 (43 hex)
Address (aa)
Figur
e C-35
Command
67 — Request
I000000
Response: aa 43 bb dddd . . . XXXX
Checksum (XXXX)
WY memory data
Number of data bytes to follow (bb)
Command 67 (43 hex)
PLC TIWAY network address (aa)
Figur
e C-36
Command
67 — Response
Command 66 —
Read K Memory
Command 67 —
Read WY Memory
Vue de la page 75
1 2 ... 71 72 73 74 75 76 77 78 79 80 81 ... 93 94

Commentaires sur ces manuels

Pas de commentaire