Product information CP 3431
C79000Z8964C03805
2.3 Attaching the CP 343-1 to Industrial Ethernet
The CP 343-1 can be attached to Industrial Ethernet using a
S Transceiver with an AUI interface
Transceiver cable
(drop cable) 727-1
Transceiver
SF
RUN
STOP
R
STOP
RUN
CP 3431
Figure 3 Attaching the CP 343-1 to Industrial Ethernet with AUI/Transceiver
The CP 343-1 generates and supplies the 13 V power required by the
transceiver.
S Industrial Twisted Pair attachment, for example using a Optical Switch
Module (OSM) or hub.
When using the Industrial Ethernet installation cable shown in Figure 4,
the CP 343-1 automatically switches over to Twisted Pair. Information
about the pinout can be found at the end of this section.
With Industrial Twisted Pair, cables with a length of up 100 m can be
installed between the CP and Optical Switch Module (OSM).