Siemens KDN Series Instructions d'exploitation Page 56

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 258
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 55
KINCO
56
NoteChange the value of 8-30 to 2 on the Danfoss Frequency Converter for modbus protocol
Change the value of 8-30 to 0 for the Danfoss Protocol
Frequency Converter
8-3* FC Port Setting
8-30 protocol
*[0] FC (danfoss protocol)
[2] Modbus (modbus protocol)
8-31 address
1 – 247 * 1 (HMI station No.)
8-32 FC Port Baud Rate
[0] 2400 Baud
[1] 4800 Baud
*[2] 9600 Baud
8-33 FC Port Parity
*[0] even, 1 stop bit
[1] Odd, 1 stop bit
[2] None, 1 stop bit
[3] None, 2 stop bit
Frequency Converter setting
Please refer to the manual of Danfoss Frequency Converter for details
Supported Device
Danfoss Protocol:
Device Bit Address Word Address Format
EEPROM Register(Double Word) ———— EPD0-7998.99999 DDDD.DDDDD
EEPROM Register ———— EPW0-7998.99999 DDDD.DDDDD
Vue de la page 55
1 2 ... 51 52 53 54 55 56 57 58 59 60 61 ... 257 258

Commentaires sur ces manuels

Pas de commentaire