Siemens HS Spécifications Page 30

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 61
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 29
Interrupts/diagnostics alarms
5.2 Interrupts
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Manual, 07/2014, A5E03484886-AC
29
5.2
Interrupts
Analog input module AI 8xU/I HS supports the following diagnostic and hardware interrupts.
Diagnostic interrupt
The module generates a diagnostic interrupt at the following events:
Missing supply voltage L+
Wire break
Overflow
Underflow
Hardware interrupt
The module generates a hardware interrupt at the following events:
Low limit violated 1
High limit violated 1
Low limit violated 2
Violation of high limit 2
For detailed information on the error event, refer to the hardware interrupt organization block
with the "RALRM" instruction (read additional interrupt info) and to the STEP 7 online help.
The module channel that triggered the hardware interrupt is entered in the start information
of the organization block. The diagram below shows the assignment to the bits of double
word 8 in local data.
Figure 5-2 OB start information
Vue de la page 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 60 61

Commentaires sur ces manuels