SED2 VFD Parameter Reference Guide
16 Siemens Building Technologies, Inc.
Parameter Details (Numeric
Listing)
r0000 Drive display Level 1
Min: - Def: - Max: -
Unit: -
Details:
Displays user-selected output, defined via P0005.
Note:
Pressing the Fn button for 2 seconds allows you to view the values of DC link
voltage, output frequency, output current, and the selected r0000 setting (defined
via P0005).
r0002 Drive state Level 3
Min: - Def: - Max: -
Unit: -
Details:
Displays actual SED2 state.
Enum:
0 Commissioning mode (P0010=0)
1 SED2 ready
2 SED2 fault active
3 SED2 starting (DC-link precharging)
4 SED2 running
5 Stopping (ramping down)
Dependency:
State 3 is visible only while precharging the DC link and when an externally
powered communications module is installed.
P0003 User access level Level 1
Min: 0 Def: 1 Max: 4
Unit: -
Details:
Defines user access level to parameters. The default setting (standard) is
sufficient for most simple applications.
Enum:
0 User-defined parameter list; see P0013 for details.
1 Standard: For access to the most frequently used parameters.
2 Extended: For access to additional parameters for supplemental operations
such as SED2 I/O functions.
3 Expert: For skilled, authorized users familiar with SED2 operations and
functions.
4 Service: For use by trained, authorized service personal only; password
protected.