The FS-250 addressable fire alarm control panel is a
small, low cost fire alarm panel suited for stand-alone
operation in small to medium sized facilities. It features a
single addressable input device circuit and four notification
appliance circuits. The system is available with both a
black or red enclosure, with operating controls and
indicators behind a locked door. The FS-250 is Listed
by Underwriters Laboratories.
Main System
The FS-250 indicates alarm, trouble and supervisory
conditions with an 80 character backlit LCD display and
integral system status LEDs. Acknowledge, alarm
silence, and system reset are accomplished with
built-in membrane control buttons. Basic user and
4306
CATALOG NUMBER
• One intelligent signaling line circuit (Style 4 or 6)
• SureWire polarity insensitive loop wiring
• Utilizes H-Series detectors and devices
• Supports up to 252 addressable inputs AND
signal/relay outputs
• Devices operate on standard wire, no twist
or shield required
• FirePrint application specific fire detection
• 4 Class B/2 Class A NAC circuits
• Up to 6 amps of NAC power
• Built in strobe synchronization protocol
• One man walk test (silent or audible)
• 80 Character backlit LCD display
• Optional internal DACT capable of transmitting
point or group information
• Programmable from front keypad or Windows
based PC configuration tool
• Built in RS-232 port for computer programming
• 2000 event history log
• Alarm, trouble, supervisory and power fail
relays built-in
• Auto program feature makes system start-up faster
• Maintenance and technician level passwords
, MEA and CSFM listed
FireSeeker Model FS-250
Addressable Fire Alarm Control Panel
maintenance level functions such as viewing history or
system enable/disable are also accomplished through the
membrane control buttons. Password protection of
maintenance level functions is present. The main system
can support up to 38 AH battery sets, up to 10 AH will fit
inside the enclosure.
The basic FS-250 features a single addressable signaling
line circuit (Style 4 or 6) capable of supporting up to 252
addressable input devices, whether they are detectors,
manual pull stations, or contact monitoring points. Each
detector can also have an optional audible detector base,
relay detector base, or remote lamp associated with it.
These auxiliary devices are completely controlled through
logic, and are not required to activate simultaneously with
the detector.