6
Introduction 2000585-001
DataNET Hub Specifications
Dimensions Rack Mounted Package Configuration
See Figure 1-5 for Outline Drawing and Dimensions
Wall-Mounted Package Configuration
See Figure 1-6 for Outline Drawing and Dimensions
Zone 1 - Wall-Mounted Package Configuration
See Figure 1-7 for Outline Drawing and Dimension
Housing, Explosion Protection,
Ratings and Certifications
Wall Mounted Configuration
NEMA 3 (IP-54)
CSA Certified for Class I, Division 2, Group A,B,C,D
CENELEC non-Ex
(Air purge is not required for fire protection as indicated; however, the
unit may be air purged, if desired, for additional protection from envi-
ronmental elements.)
Rack Mounted Configuration
NEMA 2 (IP-20)
CSA Certified for Class I, Division 2, Group A,B,C,D
CENELEC non-Ex
Zone 1 Configurations
CENELEC approved EEx d IIC T6 Cortem CCA-04 enclosure
Electromagnetic and Radio Frequency Compatibility and Electrical
Safety
CE Compliance; certified to 89/336/ECC (EMC directive)
CE Compliance; certified to 73/23/EEC (Low Voltage directive)
Tested per EN 61010-1 / IEC 1010-1
Housing Materials and Colors
Stainless steel (1.4016); Front and top are commercial gray B
(RAL 7043), housing is light gray (RAL 7035)
Weight
Rack/Wall: 15 kg (35 pounds) approximately
Zone 1: 33 kg (73 pounds)