Siemens sitrans LU01 Manuel d'instructions Page 96

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 114
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 95
Page 90 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02
mmmmm
Technical Reference
Example 1 - Level Measurement
Material Level
This is the most common application of the SITRANS LU01 level monitor.
For this example we'll assume the following:
one 30 m high cement silo is to be monitored.
the maximum vessel filling rate is 0.08 m per minute.
alarm indicators are required when the cement level exceeds 25 m or falls below
10 m.
filling equipment is to be automatically deactivated at 27 m.
in the event of a measurement difficulty, failsafe operation is to be activated in 2
minutes.
if the difficulty doesn't subside, the filling process is to be stopped before a spill
occurs.
an XLT-30 transducer is mounted with its face flush with the top of the vessel.
a TS-3 temperature sensor is connected to the Temp Sensor 1 terminals.
transducer
5.00 m
(P104)
10.00 m
(P102)
27.00 m
(P103)
25.00 m
(P101)
30.00 m
(P006)
29.01 m
(P007)
Vue de la page 95
1 2 ... 91 92 93 94 95 96 97 98 99 100 101 ... 113 114

Commentaires sur ces manuels

Pas de commentaire