Analog Modules
5-103
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Data for Selecting a Sensor
Input range (rated values)/Input
resistance
Voltage " 1 V/10 M
" 10 V/100 M
1 V to 5 V100 M
Current " 20 mA/50
4 mA to 20 mA50
Maximum input voltage for
voltage input
(destruction limit)
20 V continuous;
75 V for 1 ms (cycle
factor 1 : 20)
Maximum input current for
current input (destruction limit)
40 mA
Connection of the signal
sensor
For measuring voltage Possible
For measuring current
As two-wire
transmitter
Possible
As four-wire
transmitter
Possible
Load of the two-wire
transmitter
Max. 750
Characteristic linearization No
Vue de la page 318