SB Solenoid Coil Resistances
SHUNT TRIP SOLENOID:
Shunt Trip Plunger O.D. = 0.310 inch
+/– 5% @ 20 degrees C
12 VDC – 3.6 ohms 120 VAC – 79.6 ohms
24 VDC – 14.2 ohms 240 VAC – 380 ohms
48 VDC – 55 ohms 480 VAC – 1163 ohms
125 VDC – 370 ohms
Shunt Trip Plunger O.D. = 0.437 inch
+/– 10% @ 20 degrees C
12 VDC – 4.3 ohms 120 VAC – 14 ohms
24 VDC – 9 ohms 240 VAC – 48 ohms
48 VDC – 34 ohms
125 VDC – 225 ohms
UNDERVOLTAGE RELAY SOLENOIDS:
+/– 5% @ 20 degrees C
12 VDC – 117 ohms 48 VDC – 1822 ohms
24 VDC – 460 ohms 125 VDC – 11,395 ohms*
*125 VDC Solenoid used for all VAC UVR Applications.
ELECTRIC OPERATOR CLOSING SOLENOIDS:
+/– 10% @ 20 degrees C
24 VDC – 1.28 ohms 120 VDC – 35 ohms
48 VDC – 5.20 ohms 125 VDC – 35 ohms
REMOTE CLOSE SOLENOIDS:
+/– 10% @ 20 degrees C
24 VDC – 1.28 ohms 120 VDC – 14 ohms
48 VDC – 5.20 ohms 125 VDC – 35 ohms
PRIMARY CURRENT INJECTION AND FIELD TESTING SB BREAKERS
All field testing should be in accordance with NEMA Standards Publication No. AB4.