G3 Electronics
00497GB-2009/R01
Availability, design and specifi cations are subject to change without notice. All rights reserved.
X024 - 6
www.asconumatics.eu
DeviceNet™
DeviceNet™ is an open bus fieldbus communication
system developed by Allen-Bradley based on Controller
Area Network (CAN) technology. The governing body for
DeviceNet™ is the Open DeviceNet™ Vendors Association
(ODVA). The ODVA controls the DeviceNet™ specification
and oversees product conformance testing.
Numatics’ G3 DeviceNet™ nodes have an integrated
graphic display and are capable of addressing combinations
of up to 544 Inputs / Outputs.
They have been tested and approved for conformance by
the ODVA.
More information about DeviceNet™ and the ODVA can be
obtained from the following WEB site:
www.odva.org
Technical Data
ELECTRICAL DATA VOLTAGE CURRENT
Node Power at Max. Brightness 24 VDC +/- 10% 0.070 Amps
BUS Power 11-25 VDC 0.025 Amps
Valves & Discrete I/O 24 VDC +/- 10% 8 Amps Maximum
Power Connector Single key 4 pin 7/8" MINI type (male)
Communication Connector Single key 5 pin 7/8" MINI type (male)
LED's Module Status and Network Status
OPERATING DATA
Temperature Range (ambient) -23º to +50º C
Humidity 95% relative humidity, non-condensing
Vibration / Shock IEC 60068-2-27, IEC60068-2-6
Moisture Protection IP65, IP67 (with appropriate assembly and termination)
CONFIGURATION DATA
Graphic Display Display used for setting Node Address, Baud Rate, Fault / Idle Actions, DeviceNet QuickConnect and all other system settings.
MCM (Manual Confi guration Module) Optional module containing DIP switches for setting node address and baud rate.
ARM (Auto Recovery Module) Optional module that contains automatic recovery of system setting in the event of total or partial system failure.
Maximum Valve-Solenoid Outputs 32
Maximum Addressable I/O Points Various combinations of 544 inputs / outputs (1200 bits)
NETWORK DATA
Supported Baud Rates 125K Baud, 250K Baud, 500K Baud, with Auto-Baud detection
Supported Connection Type Polled, Cyclic, Change of State (COS) and combination Message Capability
Bus Connector Single key 5 pin 7/8" MINI type (male)
Diagnostics Power, short, open load conditions and module health are monitored
Special Features Supports Auto-Device Replacement (ADR) and fail-safe device settings
WEIGHT
DeviceNet Communication Module 252g / 8.9 oz.
DESCRIPTION
REPLACEMENT
PART NUMBER
DeviceNet
communications
module (node)
240-180
DeviceNet™
COMM MALE
Pin 1 = Shield
Pin 2 = V+ (24 VDC)
Pin 3 = V- (Ground)
Pin 4 = CAN_H
Pin 5 = CAN_L
POWER MALE
Pin 1 = +24 VDC (valves & out)
Pin 2 = +24 VDC (node & in)
Pin 3 = 0 VDC (node & in)
Pin 4 = 0 VDC (valves & out)