Siemens ET 7Y Series Spécifications Page 87

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 214
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 86
Commissioning and Diagnostics
7-5
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
t
On
Off
3 s
Max. 3 s
Min. 3 s
1st 2. 3.
STOP
LED
STOP
MRES
RUN
STOP
MRES
RUN
STOP
MRES
RUN
STOP
MRES
RUN
STOP
MRES
RUN
Figure 7-1 How to use the mode selector to reset the memory
Is the STOP LED not flashing at memory resetting?
Does the STOP LED not flash during memory reset or do other indicators come
on? You must repeat steps 2 and 3. If the IM 151-7 CPU still doesnt execute a
memory reset, you have to read out the diagnostic buffer of the CPU with the PD
(see the STEP 7 user manual).
What happens in the IM 151-7 CPU?
Table 7-3 Internal CPU events at memory resetting
Event Response of the CPU in the IM 151-7 CPU
Sequence of
operations in the
IM 151-7 CPU
1. The CPU deletes the entire user program in the working memory
and the RAM load memory.
2. The CPU deletes the retentive data.
3. The CPU tests its own hardware.
4. If you have inserted a memory module (micro memory card =
MMC), the CPU copies the relevant contents of the module to
the working memory.
Memory contents
after reset
The CPU has the memory level ”0”. If a SIMATIC micro memory card
is inserted, the user program is transferred back into the working
memory.
What’s left? The contents of the diagnostic buffer and the runtime meter.
Vue de la page 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 213 214

Commentaires sur ces manuels

Pas de commentaire