Connecting up
SCALANCE W788-xPRO / W74x-1PRO/RR
32 A5E02280448-02, Release 11/2008
Fitting the IE FC TP standard cable 4 x 2 GP to an IE
IP 67 hybrid connector
Procedure
Remove the two inner shells of the universal
sealing ring to adapt it to the diameter of the
hybrid cable.
Push the bushing, washer, adapted universal
sealing ring and the housing over the cable
jacket.
25 mm
30 mm
Remove the following lengths of cable jacket
and shield braid:
25 mm for the power leads
30 mm for the data leads
To achieve good shielding, the shield braid
must be alt least 30 mm long.