INTRODUCTION
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2002/2003
Version D 1/4
1.3 Conformity to International Standards
1.3.1 CE Mark:
The MICROMASTER, MICROMASTER Vector and MIDIMASTER Vector drive inverters fulfill the requirements of the Low-Voltage
Directive 73/23/EC and therefore have the CE Mark. A certificate of conformance can be issued when required. The drive units are
certified in compliance with the following Standards:
EN60204-1 Safety of Machinery, Electrical Equipment of Machines
EN60146-1-1 Semiconductor inverters; General requirements and line commutated inverters
1.3.2 Electromagnetic compatibility:
MICROMASTER, MICROMASTER Vector and MIDIMASTER Vector drive inverters, fulfill, when correctly installed and used in-line with
the specifications, the requirements of Directive 89/336/EC regarding electromagnetic compatibility. When all of the Guidelines to reduce
the effects of electromagnetic radiation are followed when installing the drive units, then all of the requirements for the CE certification of a
machine will be fulfilled.
The following table lists the results (measured) with reference to emission and noise immunity of the MICROMASTER,
MICROMASTER Vector and MIDIMASTER Vector drive inverters. The drive inverters were installed corresponding to the
appropriate guidelines using shielded motor cables, shielded control cables and the line filters which are available as
accessory (with the exception of single-phase units):
Test Measurement Test value Limit value acc. to
EN50081/EN50082
HF noise EN55011 (VDE0875 Part 11) and
EN55022 (VDE 0878 Part 22)
Conducted through the line supply
cable and radiated through air
1/3 phase 230/400/460V AC with
integrated filter >= Class A
1/3 phase with external filter >= Class B
(only cable-borne noise)
Class A
Class B
ESD immunity
EN61000-4-2 (VDE 0847 Part 4-2)
ESD through air discharge
ESD through contact discharge
Level 4: 15 kV
Level 4: 8 kV
8 kV
4 kV
Immunity to electric fields
EN61000-4-3 (VDE 0847 Part 4-3)
Electric field is applied to the unit 10 V/m 26-1000 MHz 10 V/m
Noise immunity to noise pulses (burst)
EN61000-4-4 (VDE 0847 Part 4-4)
Connected to all cable
connections:
Line supply cable
Motor cable
Control cables
Braking resistor/module cable
DC link cable
Level 4: 4 kV
Level 4: 4 kV
4 kV
Level 4: 4 kV
Level 4: 4 kV
2 kV
2 kV
2 kV
2 kV
2 kV
Surge immunity
EN61000-4-5 (VDE 0847 Part 4-5)
Connected to all line supply cables: 4 kV non-symmetrical
2 kV symmetrical
4 kV non-symmetrical
2 kV symmetrical
Table 2: EMC conformity