Siemens RDG160KN Manuel de service Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 21
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
Commissioning notes
The room thermostats are delivered with a fixed set of applications.
Select and activate the relevant application during commissioning using one of the
following tools:
Local DIP switch and HMI
Synco ACS
ETS
Set the DIP switches before snapping the thermostat to the mounting plate, if you
want to select an application via DIP switches.
All DIP switches need to be set to “OFF” ("remote configuration"), if you want to
select an application via commissioning tool.
After power is applied, the thermostat resets and all LCD segments flash, indica-
ting that the reset was correct. After the reset, which takes about 3 seconds, the
thermostat is ready for commissioning by qualified HVAC staff.
If all DIP switches are OFF, the display reads "NO APPL" to indicate that
application commissioning via a tool is required.
Each time the application is changed, the thermostat reloads the factory setting for
all control parameters, except for KNX device and zone addresses!
Connect the Synco ACS or ETS tools to the KNX bus cable at any point for
commissioning:
L
N Y1
Y2
X1 M
X2
N1
3191A03
Q1 Q2
Q3
CE+ CE-
KNX
KNX
V24
ETS
RS232
Siemens
N148 /
UP146 /
UP152
KNX
USB
ETS / ACS
Siemens
OCI700
D1
GND
Y3 Y4
ACS and ETS require an interface:
RS232 KNX interface (e.g. Siemens N148 / UP146 / UP152)
OCI700 USB- KNX interface
An external KNX bus power supply is required if an RDG1...KN is connected
directly to a tool (ACS or ETS) via KNX interface.
The thermostat's control parameters can be set to ensure optimum performance of
the entire system (see basic documentation P3191).
The parameters can be adjusted using
Local HMI
Synco ACS
ETS
Applications
Note
Connect tool
Note
Control parameters
12 / 21
Siemens RDG100KN, RDG160KN Room thermostats with KNX communications CE1N3191en
Building Technologies 2014-05-23